| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly. |
| Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 passwords are sent as plaintext during unlocking and project transfers. An attacker who has network visibility can observe the password exchange. |
| Softing OPC UA C++ SDK (Software Development Kit) versions from 5.59 to 5.64 exported library functions don't properly validate received extension objects, which may allow an attacker to crash the software by sending a variety of specially crafted packets to access several unexpected memory locations. |
| An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other. |
| Navigating to a specific URL with a patient ID number will result in the server generating a PDF of a lab report without authentication and rate limiting. |
| The affected product is vulnerable due to an invalid pointer initialization, which may lead to information disclosure. |
| The affected product is vulnerable to an out-of-bounds read, which may result in disclosure of sensitive information. |
| A specially crafted packet sent to the Fernhill SCADA Server Version 3.77 and earlier may cause an exception, causing the server process (FHSvrService.exe) to exit. |
| A relative path traversal attack in the B. Braun Melsungen AG SpaceCom Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 allows attackers with service user privileges to upload arbitrary files. By uploading a specially crafted tar file an attacker can execute arbitrary commands. |
| A session fixation vulnerability in the B. Braun Melsungen AG SpaceCom administrative interface Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 allows remote attackers to hijack web sessions and escalate privileges. |
| Improper access controls in the B. Braun Melsungen AG SpaceCom Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 enables attackers to extract and tamper with the devices network configuration. |
| A reflected cross-site scripting (XSS) vulnerability in the B. Braun Melsungen AG SpaceCom Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 allows remote attackers to inject arbitrary web script or HTML into various locations. |
| A XPath injection vulnerability in the B. Braun Melsungen AG SpaceCom Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 allows unauthenticated remote attackers to access sensitive information and escalate privileges. |
| An open redirect vulnerability in the administrative interface of the B. Braun Melsungen AG SpaceCom device Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 allows attackers to redirect users to malicious websites. |
| An improper verification of the cryptographic signature of firmware updates of the B. Braun Melsungen AG SpaceCom Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 allows attackers to generate valid firmware updates with arbitrary content that can be used to tamper with devices. |
| A vulnerability in the B. Braun Melsungen AG SpaceCom Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 allows attackers to recover user credentials of the administrative interface. |
| Hard-coded credentials in the B. Braun Melsungen AG SpaceCom Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 enable attackers with command line access to access the device’s Wi-Fi module. |
| OSIsoft PI Vision 2020 versions prior to 3.5.0 could disclose information to a user with insufficient privileges for an AF attribute. |
| Automated Logic's WebCtrl Server Version 6.1 'Help' index pages are vulnerable to open redirection. The vulnerability allows an attacker to send a maliciously crafted URL which could result in redirecting the user to a malicious webpage or downloading a malicious file. |
| The affected product is vulnerable to a network-based attack by threat actors supplying a crafted, malicious XML payload designed to trigger an external entity reference call. |