| Siemens Scalance W7xx devices with firmware before 4.5.4 use the same hardcoded X.509 certificate across different customers' installations, which makes it easier for remote attackers to conduct man-in-the-middle attacks against SSL sessions by leveraging the certificate's trust relationship. |
| The login implementation in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, has a hardcoded account, which makes it easier for remote attackers to obtain access via an unspecified request. |
| HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to cause a denial of service (application crash) by sending crafted data over TCP. |
| Heap-based buffer overflow in the Siemens WinCC Runtime Advanced Loader, as used in SIMATIC WinCC flexible Runtime and SIMATIC WinCC (TIA Portal) Runtime Advanced, allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted packet to TCP port 2308. |
| The Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, exhibits different behavior for NetBIOS user names depending on whether the user account exists, which allows remote authenticated users to enumerate account names via crafted URL parameters. |
| SQL injection vulnerability in the login screen in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, allows remote attackers to execute arbitrary SQL commands via unspecified vectors. |
| Unspecified vulnerability in the client library in Siemens COMOS 9.2 before 9.2.0.6.10 and 10.0 before 10.0.3.0.4 allows local users to obtain unintended write access to the database by leveraging read access. |
| Stack-based buffer overflow in HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to execute arbitrary code via vectors related to Unicode strings. |
| A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The user privileges for the web interface are only enforced on client side and not properly verified on server side. Therefore, an attacker is able to execute privileged commands using an unprivileged account. |
| Absolute path traversal vulnerability in the ALMListView.ALMListCtrl ActiveX control in almaxcx.dll in the graphical user interface in Siemens Automation License Manager (ALM) 2.0 through 5.1+SP1+Upd2 allows remote attackers to overwrite arbitrary files via the Save method. |
| A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The implementation of SNMPv3 does not check the user credentials sufficiently. Therefore, an attacker is able to execute SNMP commands without correct credentials. |
| Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allow user-assisted remote attackers to execute arbitrary code via a crafted project file, related to the HMI web server and runtime loader. |
| Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 does not properly copy fields obtained from clients, which allows remote attackers to cause a denial of service (exception and daemon crash) via long fields, as demonstrated by fields to the (1) open_session->workstation->NAME or (2) grant->VERSION function. |
| Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to UDP port 161 (aka the SNMP port). |
| Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port). |
| Directory traversal vulnerability in the web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote authenticated users to read arbitrary files via vectors involving a query for a pathname. |
| Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 allows remote attackers to cause a denial of service (NULL pointer dereference and daemon crash) via crafted content in a (1) get_target_ocx_param or (2) send_target_ocx_param command. |
| The SSL protocol, as used in certain configurations in Microsoft Windows and Microsoft Internet Explorer, Mozilla Firefox, Google Chrome, Opera, and other products, encrypts data by using CBC mode with chained initialization vectors, which allows man-in-the-middle attackers to obtain plaintext HTTP headers via a blockwise chosen-boundary attack (BCBA) on an HTTPS session, in conjunction with JavaScript code that uses (1) the HTML5 WebSocket API, (2) the Java URLConnection API, or (3) the Silverlight WebClient API, aka a "BEAST" attack. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly represent WebNavigator credentials in a database, which makes it easier for remote authenticated users to obtain sensitive information via a SQL query. |
| The web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to obtain sensitive information or cause a denial of service via a crafted project file. |