| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| CRLF injection vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via a crafted URL. |
| Directory traversal vulnerability in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to read HMI web-application source code and user-defined scripts via a crafted URL. |
| Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to inject arbitrary web script or HTML via unspecified data. |
| Directory traversal vulnerability in the web interface in the Health Monitor service in MatrikonOPC A&E Historian 1.0.0.0 allows remote attackers to read and delete arbitrary files via a crafted URL. |
| Buffer overflow in the RegReader ActiveX control in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to execute arbitrary code via a long parameter. |
| Buffer overflow in CCEServer (aka the central communications component) in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to cause a denial of service via a crafted packet. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly assign privileges for the database containing WebNavigator credentials, which allows remote authenticated users to obtain sensitive information via a SQL query. |
| The web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to obtain sensitive information or cause a denial of service via a crafted project file. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly represent WebNavigator credentials in a database, which makes it easier for remote authenticated users to obtain sensitive information via a SQL query. |
| Directory traversal vulnerability in the web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote authenticated users to read arbitrary files via vectors involving a query for a pathname. |
| Cogent Real-Time Systems Cogent DataHub before 7.3.0, OPC DataHub before 6.4.22, Cascade DataHub before 6.4.22 on Windows, and DataHub QuickTrend before 7.3.0 allow remote attackers to cause a denial of service (NULL pointer dereference and application crash) via malformed data in a formatted text command. |
| Cogent Real-Time Systems Cogent DataHub before 7.3.0, OPC DataHub before 6.4.22, Cascade DataHub before 6.4.22 on Windows, and DataHub QuickTrend before 7.3.0 do not properly handle exceptions, which allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via malformed data in a formatted text command, leading to out-of-bounds access to (1) heap or (2) stack memory. |
| The DataSim and DataPid demonstration clients in Cogent Real-Time Systems Cogent DataHub before 7.3.0, OPC DataHub before 6.4.22, Cascade DataHub before 6.4.22 on Windows, and DataHub QuickTrend before 7.3.0 allow remote servers to cause a denial of service (incorrect pointer access and client crash) via malformed data in a formatted text command. |
| SQL injection vulnerability in Invensys Wonderware Information Server (WIS) 4.0 SP1SP1, 4.5- Portal, and 5.0- Portal allows remote attackers to execute arbitrary SQL commands via unspecified vectors. |
| Invensys Wonderware Information Server (WIS) 4.0 SP1SP1, 4.5- Portal, and 5.0- Portal does not restrict unspecified size and amount values, which allows remote attackers to execute arbitrary code or cause a denial of service (resource consumption) via unknown vectors. |
| Invensys Wonderware Information Server (WIS) 4.0 SP1SP1, 4.5- Portal, and 5.0- Portal allows remote attackers to read arbitrary files, send HTTP requests to intranet servers, or cause a denial of service (CPU and memory consumption) via an XML document containing an external entity declaration in conjunction with an entity reference, related to an XML External Entity (XXE) issue. |
| The installer routine in Schneider Electric MiCOM S1 Studio uses world-writable permissions for executable files, which allows local users to modify the service or the configuration files, and consequently gain privileges or trigger incorrect protective-relay operation, via a Trojan horse executable file. |
| Cross-site scripting (XSS) vulnerability in Invensys Wonderware Information Server (WIS) 4.0 SP1SP1, 4.5- Portal, and 5.0- Portal allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. |
| The Galil RIO-47100 Pocket PLC allows remote attackers to cause a denial of service via a session that includes "repeated requests." |
| The TFTP server on the Emerson Process Management ROC800 RTU with software 3.50 and earlier, DL8000 RTU with software 2.30 and earlier, and ROC800L RTU with software 1.20 and earlier allows remote attackers to upload files and consequently execute arbitrary code via unspecified vectors. |